Page top

Industrial Automation

Industrial Automation

3G3RX2

High-function General-purpose Inverters

3G3RX2

Save energy and maximize performance with versatile inverter

Performance Specifications

Inverter 3G3RX2

3-phase 200-V Class

Very Low Duty (VLD)/Low Duty (LD)/Normal Duty (ND)

3G3RX2-A2[][][][][] A2004 A2007 A2015 A2022 A2037
Applicable motor
(4-pole) capacity (kW)
VLD 0.75 1.5 2.2 3.7 5.5
LD 0.75 1.5 2.2 3.7 5.5
ND 0.4 0.75 1.5 2.2 3.7
Output Rated output
current (A)
VLD 4.4 8.0 10.4 15.6 22.8
LD 3.7 6.3 9.4 12.0 19.6
ND 3.2 5.0 8.0 11.0 17.5
Overload
current rating
VLD 110% 60 sec / 120% 3 sec
LD 120% 60 sec / 150% 3 sec
ND 150% 60 sec / 200% 3 sec
Rated output voltage 3-phase (3-wire) 200 to 240 V (depending on receiving voltage)
Rated
capacity
(kVA)
200 V VLD 1.5 2.8 3.6 5.4 7.9
LD 1.3 2.2 3.3 4.2 6.8
ND 1.1 1.7 2.8 3.8 6.1
240 V VLD 1.8 3.3 4.3 6.5 9.5
LD 1.5 2.6 3.9 5.0 8.1
ND 1.3 2.1 3.3 4.6 7.3
Input Rated input
current (A) *1
VLD 5.2 9.5 12.4 18.6 27.1
LD 4.4 7.5 11.2 14.3 23.3
ND 3.8 6.0 9.5 13.1 20.8
Rated input AC voltage Control power supply: Power supply single phase 200 to 240 V/allowable
variation range 170 to 264 V,
50 Hz (allowable variation range: 47.5 to 52.5 Hz)/60 Hz (allowable variation
range: 57 to 63 Hz)
Main circuit power supply: 3-phase (3-wire) 200 to 240 V/allowable variation
range 170 to 264 V,
50 Hz (allowable variation range: 47.5 to 52.5 Hz)/60 Hz (allowable variation
range: 57 to 63 Hz)
Power supply
equipment
capacity (kVA) *2
VLD 2.0 3.6 4.7 7.1 10.3
LD 1.7 2.9 4.3 5.4 8.9
ND 1.5 2.3 3.6 5.0 7.9
Carrier frequency operating
range *3
VLD 0.5 to 10.0 kHz
LD 0.5 to 12.0 kHz
ND 0.5 to 16.0 kHz
Motor start torque *4 200%/0.3 Hz
Braking Regenerative braking Equipped with BRD circuit (with a discharging resistor separately installed)
Minimum resistance that
can be connected (Ω)
50 50 35 35 35
Dimension Height (mm) 255 255 255 255 255
Width (mm) 150 150 150 150 150
Depth (mm) 140 140 140 140 140
Protective construction IP20 *5 / UL open type
Approximate mass (kg) 3 3 3 3 3

3G3RX2-A2[][][][][] A2055 A2075 A2110 A2150 A2185
Applicable motor
(4-pole) capacity (kW)
VLD 7.5 11 15 18.5 22
LD 7.5 11 15 18.5 22
ND 5.5 7.5 11 15 18.5
Output Rated output
current (A)
VLD 33.0 46.0 60.0 80.0 93.0
LD 30.0 40.0 56.0 73.0 85.0
ND 25.0 32.0 46.0 64.0 76.0
Overload
current rating
VLD 110% 60 sec / 120% 3 sec
LD 120% 60 sec / 150% 3 sec
ND 150% 60 sec / 200% 3 sec
Rated output voltage 3-phase (3-wire) 200 to 240 V (depending on receiving voltage)
Rated
capacity
(kVA)
200 V VLD 11.4 15.9 20.8 27.7 32.2
LD 10.4 13.9 19.4 25.3 29.4
ND 8.7 11.1 15.9 22.2 26.3
240 V VLD 13.7 19.1 24.9 33.3 38.7
LD 12.5 16.6 23.3 30.3 35.3
ND 10.4 13.3 19.1 26.6 31.6
Input Rated input
current (A) *1
VLD 39.3 54.8 71.4 95.2 110.7
LD 35.7 47.6 66.7 86.9 101.2
ND 29.8 38.1 54.8 76.2 90.5
Rated input AC voltage Control power supply: Power supply single phase 200 to 240 V/allowable
variation range 170 to 264 V,
50 Hz (allowable variation range: 47.5 to 52.5 Hz)/60 Hz (allowable variation
range: 57 to 63 Hz)
Main circuit power supply: 3-phase (3-wire) 200 to 240 V/allowable variation
range 170 to 264 V,
50 Hz (allowable variation range: 47.5 to 52.5 Hz)/60 Hz (allowable variation
range: 57 to 63 Hz)
Power supply
equipment
capacity (kVA) *2
VLD 15.0 20.9 27.2 36.3 42.2
LD 13.6 18.1 25.4 33.1 38.6
ND 11.3 14.5 20.9 29.0 34.5
Carrier frequency operating
range *3
VLD 0.5 to 10.0 kHz
LD 0.5 to 12.0 kHz
ND 0.5 to 16.0 kHz
Motor start torque *4 200%/0.3 Hz
Braking Regenerative braking Equipped with BRD circuit (with a discharging resistor separately installed)
Minimum resistance that
can be connected (Ω)
16 10 10 7.5 7.5
Dimension Height (mm) 260 260 260 390 390
Width (mm) 210 210 210 245 245
Depth (mm) 170 170 170 190 190
Protective construction IP20 *5 / UL open type
Approximate mass (kg) 6 6 6 10 10

3G3RX2-A2[][][][][] A2220 A2300 A2370 A2450 A2550
Applicable motor
(4-pole) capacity (kW)
VLD 30 37 45 55 75
LD 30 37 45 55 75
ND 22 30 37 45 55
Output Rated output
current (A)
VLD 124 153 185 229 295
LD 113 140 169 210 270
ND 95.0 122 146 182 220
Overload
current rating
VLD 110% 60 sec / 120% 3 sec
LD 120% 60 sec / 150% 3 sec
ND 150% 60 sec / 200% 3 sec
Rated output voltage 3-phase (3-wire) 200 to 240 V (depending on receiving voltage)
Rated
capacity
(kVA)
200 V VLD 43.0 53.0 64.1 79.3 102.2
LD 39.1 48.5 58.5 72.7 93.5
ND 32.9 42.3 50.6 63.0 76.2
240 V VLD 51.5 63.6 76.9 95.2 122.6
LD 47.0 58.2 70.3 87.3 112.2
ND 39.5 50.7 60.7 75.7 91.5
Input Rated input
current (A) *1
VLD 147.6 182.1 220.2 272.6 351.2
LD 134.5 166.7 201.2 250.0 321.4
ND 113.1 145.2 173.8 216.7 261.9
Rated input AC voltage Control power supply: Power supply single phase 200 to 240 V/allowable
variation range 170 to 264 V,
50 Hz (allowable variation range: 47.5 to 52.5 Hz)/60 Hz (allowable variation
range: 57 to 63 Hz)
Main circuit power supply: 3-phase (3-wire) 200 to 240 V/allowable variation
range 170 to 264 V,
50 Hz (allowable variation range: 47.5 to 52.5 Hz)/60 Hz (allowable variation
range: 57 to 63 Hz)
Power supply
equipment
capacity (kVA) *2
VLD 56.3 69.4 83.9 103.9 133.8
LD 51.3 63.5 76.7 95.3 122.5
ND 43.1 55.3 66.2 82.6 99.8
Carrier frequency operating
range *3
VLD 0.5 to 10.0 kHz
LD 0.5 to 12.0 kHz
ND 0.5 to 16.0 kHz
Motor start torque *4 200%/0.3 Hz
Braking Regenerative braking Equipped with BRD circuit
(with a discharging resistor
separately installed)
Regenerative braking unit separately
installed
Minimum resistance that
can be connected (Ω)
5 --- --- --- ---
Dimension Height (mm) 390 540 550 550 700
Width (mm) 245 300 390 390 480
Depth (mm) 190 195 250 250 250
Protective construction IP20 *5 / UL open type
Approximate mass (kg) 10 22 33 33 47

*1. The rated input currents shown in the table are the values when the rated current is output. The values vary depending
      on impedance on the power supply (wiring, breaker, input reactor option, etc.)
*2. The power supply equipment capacities shown in the table are the values when 220 V rated current is output. The values
      vary depending on impedance on the power supply (wiring, breaker, input reactor option, etc.)
*3. The setting of rated values for carrier frequencies [bb101]/[bb201] are internally limited in accordance with the
      description. Also, it is recommended to set values equivalent to or above (maximum output frequency for driving ×10)
      Hz for the setting of carrier frequencies [bb101]/[bb201]. Also, in the case of induction motor (IM) control, for items
      other than those subject to V/f control, it is recommended to set carrier frequency at 2 kHz or more. In the case of
      synchronous motor (SM)/permanent magnet motor (PMM) control, it is recommended to set carrier frequency at 8 kHz
      or more.
*4. The value of the sensor-less vector control applied to the ND rating in the Standard motor. Torque characteristics may
      vary depending on the control method and the motor used.
*5. Based on self declaration.

3-phase 400-V Class

Very Low Duty (VLD)/Low Duty (LD)/Normal Duty (ND)

3G3RX2-[][][][][] A4007 A4015 A4022 A4037 A4055 A4075
Applicable motor
(4-pole) capacity (kW)
VLD 1.5 2.2 3.7 5.5 7.5 11
LD 1.5 2.2 3.7 5.5 7.5 11
ND 0.75 1.5 2.2 3.7 5.5 7.5
Output Rated output
current (A)
VLD 4.1 5.4 8.3 12.6 17.5 25.0
LD 3.1 4.8 6.7 11.1 16.0 22.0
ND 2.5 4.0 5.5 9.2 14.8 19.0
Overload
current rating
VLD 110% 60 sec / 120% 3 sec
LD 120% 60 sec / 150% 3 sec
ND 150% 60 sec / 200% 3 sec
Rated output voltage 3-phase (3-wire) 380 to 500 V (depending on receiving voltage)
Rated
capacity
(kVA)
400 V VLD 2.8 3.7 5.8 8.7 12.1 17.3
LD 2.1 3.3 4.6 7.7 11.1 15.2
ND 1.7 2.8 3.8 6.4 10.3 13.2
500 V VLD 3.6 4.7 7.2 10.9 15.2 21.7
LD 2.7 4.2 5.8 9.6 13.9 19.1
ND 2.2 3.5 4.8 8.0 12.8 16.5
Input Rated input
current (A) *1
VLD 4.9 6.4 9.9 15.0 20.8 29.8
LD 3.7 5.7 8.0 13.2 19.0 26.2
ND 3.0 4.8 6.5 11.0 17.6 22.6
Rated input AC voltage Control power supply: Power supply single phase 380 to 500 V (allowable
variation range 323 to 550 V),
50 Hz (allowable variation range: 47.5 to 52.5 Hz)/60 Hz (allowable variation
range: 57 to 63 Hz)
Main circuit power supply: 3-phase (3-wire) 380 to 500 V (allowable variation
range) 323 to 550 V,
50 Hz (allowable variation range: 47.5 to 52.5 Hz)/60 Hz (allowable variation
range: 57 to 63 Hz)
Power supply
equipment
capacity (kVA) *2
VLD 3.7 4.9 7.5 11.4 15.9 22.7
LD 2.8 4.4 6.1 10.1 14.5 20.0
ND 2.3 3.6 5.0 8.3 13.4 17.2
Carrier frequency range *3 VLD 0.5 to 10.0 kHz
LD 0.5 to 12.0 kHz
ND 0.5 to 16.0 kHz
Motor start torque *4 200%/0.3 Hz
Braking Regenerative braking Equipped with braking resistance circuit
(with a discharging resistor separately installed)
Minimum resistance that
can be connected (Ω)
100 100 100 70 70 35
Dimen-
sion
Height (mm) 255 255 255 255 260 260
Width (mm) 150 150 150 150 210 210
Depth (mm) 140 140 140 140 170 170
Protective construction IP20 *5 / UL open type
Approximate mass (kg) 3 3 3 3 6 6

3G3RX2-[][][][][] A4110 A4150 A4185 A4220 A4300 A4370
Applicable motor
(4-pole) capacity (kW)
VLD 15 18.5 22 30 37 45
LD 15 18.5 22 30 37 45
ND 11 15 18.5 22 30 37
Output Rated output
current (A)
VLD 31.0 40.0 47.0 62.0 77.0 93.0
LD 29.0 37.0 43.0 57.0 70.0 85.0
ND 25.0 32.0 39.0 48.0 61.0 75.0
Overload
current rating
VLD 110% 60 sec / 120% 3 sec
LD 120% 60 sec / 150% 3 sec
ND 150% 60 sec / 200% 3 sec
Rated output voltage 3-phase (3-wire) 380 to 500 V (depending on receiving voltage)
Rated
capacity
(kVA)
400 V VLD 21.5 27.7 32.6 43.0 53.3 64.4
LD 20.1 25.6 29.8 39.5 48.5 58.9
ND 17.3 22.2 27.0 33.3 42.3 52.0
500 V VLD 26.8 34.6 40.7 53.7 66.7 80.5
LD 25.1 32.0 37.2 49.4 60.6 73.6
ND 21.7 27.7 33.8 41.6 52.8 65.0
Input Rated input
current (A) *1
VLD 36.9 47.6 56.0 73.8 91.7 110.7
LD 34.5 44.0 51.2 67.9 83.3 101.2
ND 29.8 38.1 46.4 57.1 72.6 89.3
Rated input AC voltage Control power supply: Power supply single phase 380 to 500 V (allowable
variation range 323 to 550 V),
50 Hz (allowable variation range: 47.5 to 52.5 Hz)/60 Hz (allowable variation
range: 57 to 63 Hz)
Main circuit power supply: 3-phase (3-wire) 380 to 500 V (allowable variation
range) 323 to 550 V,
50 Hz (allowable variation range: 47.5 to 52.5 Hz)/60 Hz (allowable variation
range: 57 to 63 Hz)
Power supply
equipment
capacity (kVA) *2
VLD 28.1 36.3 42.6 56.3 69.9 84.4
LD 26.3 33.6 39.0 51.7 63.5 77.1
ND 22.7 29.0 35.4 43.5 55.3 68.0
Carrier frequency range *3 VLD 0.5 to 10.0 kHz
LD 0.5 to 12.0 kHz
ND 0.5 to 16.0 kHz
Motor start torque *4 200%/0.3 Hz
Braking Regenerative braking Equipped with braking resistance circuit
(with a discharging resistor separately installed)
Minimum resistance that
can be connected (Ω)
35 24 24 20 15 15
Dimen-
sion
Height (mm) 260 390 390 390 540 550
Width (mm) 210 245 245 245 300 390
Depth (mm) 170 190 190 190 195 250
Protective construction IP20 *5 / UL open type
Approximate mass (kg) 6 8.5 8.5 8.5 22 31

3G3RX2-[][][][][] A4450 A4550 B4750 B4900 B411K B413K
Applicable motor
(4-pole) capacity (kW)
VLD 55 75 90 110 132 160
LD 55 75 90 110 132 160
ND 45 55 75 90 110 132
Output Rated output
current (A)
VLD 116 147 176 213 252 316
LD 105 135 160 195 230 290
ND 91.0 112 150 180 217 260
Overload
current rating
VLD 110% 60 sec / 120% 3 sec
LD 120% 60 sec / 150% 3 sec
ND 150% 60 sec / 200% 3 sec
Rated output voltage 3-phase (3-wire) 380 to 500 V (depending on receiving voltage)
Rated
capacity
(kVA)
400 V VLD 80.4 101.8 121.9 147.6 174.6 218.9
LD 72.7 93.5 110.9 135.1 159.3 200.9
ND 63.0 77.6 103.9 124.7 150.3 180.1
500 V VLD 100.5 127.3 152.4 184.5 218.2 273.7
LD 90.9 116.9 138.6 168.9 199.2 251.1
ND 78.8 97.0 129.9 155.9 187.9 225.2
Input Rated input
current (A) *1
VLD 138.1 175.0 209.5 253.6 300.0 376.2
LD 125.0 160.7 190.5 232.1 273.8 345.2
ND 108.3 133.3 178.6 214.3 258.3 309.5
Rated input AC voltage Control power supply: Power supply single phase 380 to 500 V (allowable
variation range 323 to 550 V),
50 Hz (allowable variation range: 47.5 to 52.5 Hz)/60 Hz (allowable variation
range: 57 to 63 Hz)
Main circuit power supply: 3-phase (3-wire) 380 to 500 V (allowable variation
range) 323 to 550 V,
50 Hz (allowable variation range: 47.5 to 52.5 Hz)/60 Hz (allowable variation
range: 57 to 63 Hz)
Power supply
equipment
capacity (kVA) *2
VLD 105.2 133.4 159.7 193.2 228.6 286.7
LD 95.3 122.5 145.2 176.9 208.7 263.1
ND 82.6 101.6 136.1 163.3 196.9 235.9
Carrier frequency range *3 VLD 0.5 to 10.0 kHz 0.5 to 8.0 kHz
LD 0.5 to 12.0 kHz 0.5 to 8.0 kHz
ND 0.5 to 16.0 kHz 0.5 to 10.0 kHz
Motor start torque *4 200%/0.3 Hz 180%/0.3 Hz
Braking Regenerative braking Regenerative braking unit separately installed
Minimum resistance that
can be connected (Ω)
10 10 --- --- --- ---
Dimen-
sion
Height (mm) 550 550 700 700 740 740
Width (mm) 390 390 390 390 480 480
Depth (mm) 250 250 270 270 270 270
Protective construction IP20 *5 / UL open type IP00 / UL open type
Approximate mass (kg) 31 31 41 41 53 53

*1. The rated input currents shown in the table are the values when the rated current is output. The values vary depending
      on impedance on the power supply (wiring, breaker, input reactor option, etc.)
*2. The power supply equipment capacities shown in the table are the values when 220 V rated current is output. The values
      vary depending on impedance on the power supply (wiring, breaker, input reactor option, etc.)
*3. The setting of rated values for carrier frequencies [bb101]/[bb201] are internally limited in accordance with the
      description. Also, it is recommended to set values equivalent to or above (maximum output frequency for driving ×10)
      Hz for the setting of carrier frequencies [bb101]/[bb201]. Also, in the case of induction motor (IM) control, for items
      other than those subject to V/f control, it is recommended to set carrier frequency at 2 kHz or more. In the case of
      synchronous motor (SM)/permanent magnet motor (PMM) control, it is recommended to set carrier frequency at 8 kHz
      or more.
*4. The value of the sensor-less vector control applied to the ND rating in the Standard motor. Torque characteristics may
      vary depending on the control method and the motor used.
*5. Based on self declaration.

Function Specifications

Inverter 3G3RX2

Item Specifications
Control mode
(output to the motor)
Sine wave PWM control voltage output (line sine wave modulation)
Output frequency range *1 0.00 to 590.00 Hz
Frequency accuracy Digital command ±0.01% and analog command ±0.2% (25°C±10°C) against the
maximum frequency
Frequency resolution Digital setting: 0.01 Hz
Analog setting: maximum frequency/4000
(Ai1 terminal/Ai2 terminal: 12 bit/0 to +10 V or 0 to +20 mA, Ai3 terminal 12 bit/
-10 to +10 V)
Control mode
(frequency/voltage calculation) *2
IM V/f control (fixed torque/reduced torque/free),
automatic boost control, cascade model
sensorless vector control, 0 Hz range
sensorless vector control, vector control with
sensor.
SM/PMM Synchronous starting sensorless vector
control, IVMS starting smart sensorless vector
control
Speed fluctuation *3 ±0.5% (during sensorless vector control)
Acceleration or deceleration time 0.00 to 3600.00 sec (linear, S-shaped, U-shaped, reverse U-shaped, EL-S
shaped)
Display monitor Output frequency, output current, output torque, trip history, I/O terminal status,
I/O power *4, P-N voltage.
Starting functions Start after DC braking, frequency collection start, frequency entrainment start,
reduced voltage start, retry start
Stopping functions Free-run stop, DC braking after deceleration stop or terminal DC braking (braking
power, operating speed adjustment)
Stall prevention function Overload restraining function, overcurrent suppression function, overvoltage
suppression function
Protective function *5 Overcurrent error, Motor overload error, Braking resister Overload error,
Overvoltage error, Memory error, Undervoltage error, Current detector error, CPU
error, External trip error, USP error, Ground fault error, Incoming over voltage
error, Instantaneous power failure error, Temperature detector error, Cooling fan
rotation speed reduction temperature error, Temperature error, Input open-phase
error, IGBT error, Output open-phase error, Thermistor error, Brake error, Low-
speed range overload error, Controller overload error, RS485 communication
error, Operator keypad disconnection error.
Other functions V/f free settings (7 points), Upper/lower limit frequency limiter, Frequency jump,
Curve acceleration/deceleration, Manual torque boost, Energy-saving operation,
Analog output adjustment function, Minimum frequency, Carrier frequency
adjustment, Motor electronic thermal function (free setting is also possible),
Inverter electronic thermal function, External start/end (volume/ratio), Frequency
input selection, Trip retry, Restart after instantaneous stop, Output of signals,
Initialization settings, PID control, Automatic deceleration at power shut-off, Brake
control function, and Auto-tuning for commercial switching function (online/offline).
Input Fre-
quency
setting
Standard
operator
keypad
Parameter setting using arrow keys
External
signals *6
Ai1/Ai2 terminal (when changing
voltage)
Setting through input of 0 to 10 VDC voltage
(input impedance: 10 kΩ)
Ai1/Ai2 terminal (when changing
current)
Setting through input of 0 to 20 mA current
(input impedance: 100 Ω)
Ai3 terminal Setting through input of -10 to +10 V voltage
(input impedance: 10 kΩ)
Multistage speed terminal (use
of input terminal function)
15 speed
Pulse string input
(A/B terminal, use of input
terminal function)
32 kHz × 2 at maximum
External port Setting via RS485 serial communication (protocol: Modbus-RTU)
Normal
rotation/
reverse
rotation
Run/stop
Standard
operator
keypad
Execution with the RUN /STOP key
(normal rotation/reverse rotation can be switched by setting parameters)
External
signals
Normal rotation operation (FW)/reverse rotation (RV) (when an input terminal
function is assigned) 3-wire input available (when an input terminal function is
assigned)
External port Setting via RS485 serial communication (protocol: Modbus-RTU (maximum:
115.2 kbps)
Input terminal function 11 terminals (input of pulse string is available on terminal A and B)
FW (Normal rotation)/RV (Reverse rotation), CF1-4 (Multistage speed 1-4), SF1-7
(Multistage speed bit 1-7), ADD (Addition of frequency), SCHG (Switching of
frequency command), STA (3-wire start)/STP (3-wire stop)/F_R (3-wire normal/
reverse), AHD (Retention of analog command), FUP (Increase of speed via
remote operation/FDN (Deceleration via remote operation), UDC (Deletion of data
via remote operation), F-OP (Forced command switching), SET (Second control),
RS (Reset), JG (Jogging), DB (External current braking), 2CH (2-stage
acceleration/deceleration), FRS (Free-run stop), EXT (External abnormality), USP
(Prevention of restart after restoration of power), CS (Commercial switching), SFT
(Soft-lock), BOK (Brake check), OLR (Overload restriction switching), KHC
(Clearance of integrated input power), OKHC (Clearance of integrated output
power), PID (PID1 disabled), PIDC (PID1 integration reset), PID2 (PID2 disabled),
PIDC2 (PID2 integration reset), SVC1-4 (PID1 multistage target values 1-4), PRO
(PID gain switching), PIO (PID output switching), SLEP (SLEEP condition
satisfied)/WAKE (WAKE condition satisfied), TL (Torque restriction enabled),
TRQ1, 2 (Switching of torque limit 1, 2), PPI (Switching of P/PI control), CAS
(Switching of control gain), FOC (Preparatory excitation), ATR (Torque control
enabled), TBS (Torque bias enabled), LAC (Cancellation of acceleration/
deceleration), Mi1-11 (General-purpose input 1-11), PCC (Clearance of pulse
counter), ECOM (Start of EzCOM), PRG (Program run), HLD (Acceleration/
deceleration stop), REN (Operation permission signal), PLA (Pulse string input
A), and PLB (Pulse string input B)
Backup power supply
terminal
P+/P-: DC24V input (allowable input voltage: 24 V±10%)
STO input terminal 2 terminals (simultaneous input)
Thermistor input terminal 1 terminal (possible to switch between positive temperature coefficient/negative
temperature coefficient resistance element)
Output Output terminal
function
Transistor output 5 terminal, 1a contact relay 1 point, 1c contact relay 1 point
RUN (During operation), FA1-5 (Reached signal), IRDY (Operation ready
completion), FWR (During normal rotation operation), RVR (During reverse
rotation operation), FREF (Frequency command operator keypad), REF
(Operation command operator keypad), SETM (Second control under selection),
AL (Alarm signal), MJA (Severe failure signal), OTQ (Over torque) *7, IP (During
instantaneous power failure), UV (Under insufficient voltage), TRQ (During torque
limitation), IPS (During power failure deceleration), RNT (RUN time over), ONT
(Power on time over), THM (Electronic thermal warning), THC (Electronic thermal
warning), WAC (Capacitor life advance notice), WAF (Fan life advance notice), FR
(Operation command signal), OHF (Cooling fin heating advance notice), LOC/
LOC2 (Low-current signal), OL/OL2 (Overload advance notice), BRK (Brake
release), BER (Brake abnormality), ZS (Zero-speed detection signal), OD/OD2
(PID deviation excessive), FBV/FBV2 (PID feedback comparison), NDc
(Communication disconnection), Ai1Dc/Ai2Dc/Ai3Dc (Analog disconnection Ai1/
Ai2/Ai3), WCAi1/WCAi2/WCAi3 (Window comparator Ai1/Ai2/Ai3), LOG1-7
(Logical operation result 1-7), MO1-7 (General output 1-7), and OVS (Receiving
overvoltage).
Relay and alarm relay
(16, AL)
EDM output terminal Output for STO diagnosis
Monitor output terminal
*8
Possible to output through selection from monitor data of parameters
EMC filter switching *9 Possible to enable the EMC noise filter (switching method is different depending
on the model)
External access to PC USB Micro-B
Use
environ-
ment
Ambient temperature
*10
ND (normal duty) -10 to 50°C
LD (low duty) -10 to 45°C
VLD (very low duty) -10 to 40°C
Storage temperature
*11
-20 to 65°C
Humidity 20-90%RH (location free of condensation)
Vibration *12 5.9 m/s2 (0.6 G) 10 to 55 Hz: 3G3RX2-A2004 to A2220 / 3G3RX2-A4007 to A4220
2.94 m/s2 (0.3 G) 10 to 55 Hz: 3G3RX2-A2300 to A2550 / 3G3RX2-A4300 to
A413K
Use location *13 1000 m altitude or lower (location free from corrosive gas, oil mist, and dust)
Expected Life time Smoothing capacitor 10 years
Designed life of cooling fan 10 years (models equipped with a cooling fan) free
from dust
Memory element on the control circuit board
Applicable standards *14 Conformance to UL/cUL standards, EU Directives and UK legislation, RCM, Functional Safety SIL3/PLe, KC
Painting color Black
Operating, display LCD Operator *15
Number of option slots 3 ports
Other options Braking resistor, AC reactor, DC reactor, noise filter, EtherCAT Communication,
PG

*1. The output frequency range depend on the control and motor used. When running the inverter exceeding 60 Hz, check
      the maximum allowable frequency with the manufacturer of the motor.
*2. When the control mode is changed, unless the motor constant is appropriately configured, you cannot obtain the desired
      starting torque or the inverter may trip.
*3. The variable range of motor speed may vary depending on your system or the environment where the motor is used.
      Please contact us for details.
*4. Both the input power and output power are reference values, which are not appropriate for use in calculation of efficiency
      values, etc. To obtain an accurate value, use an external device.
*5. The IGBT error [E030] is generated by the protective function not only for short circuit protection but also when IGBT is
      damaged. Depending on the operating conditions of the inverter, the overcurrent error [E001] may occur, instead of the
      IGBT error.
*6. At the factory default setting, when voltage and current on Ai1/Ai2 terminal is changed using a switch, with input of
      voltage at 9.8 V and current at 19.8 mA, the maximum frequency is commanded. To change characteristics, make
      adjustments using the analog start/end function.
*7. The threshold for signal output varies depending on the motor to be combined with the inverter, parameter adjustment,
      etc.
*8. The output data of analog voltage monitor and analog current monitor are reference values for connecting an analog
      meter. Due to the meter to be connected and variation in analog output circuit, the maximum output value may slightly
      vary from 10 V or 20 mA. To change characteristics, make adjustments using the Ao1 adjustment and Ao2 adjustment
      functions. Some monitor data cannot be output.
*9. To enable the EMC filter, connect with a power supply grounded at a neutral point. Otherwise, the leakage current may
      increase.
*10. Use the 400 V class inverter at an input voltage of 500 VAC or below. If input voltage exceeds 500 VAC due to
        fluctuation of power, use the inverter at 40°C or lower ambient temperature.
*11. The storage temperature is the temperature during transport.
*12. To be in accordance with the testing method specified in JIS C 60068-2-6: 2010 (IEC 60068-2-6:2007)
*13. When the inverter is used in a location at 1000 m or higher altitude, air pressure reduces approximately 1% every 100
        m elevation. Perform 1% current der- ating and conduct evaluation for every 100 m elevation.
*14. For insulation distance, comply with UL and CE standards
*15. When a clock function is used, the optional battery (CR2032, 3 V) is required. When you purchase, this LCD operator
       does not come with the battery.

Communication Unit

The EtherCAT Communication Unit is an interface unit. When installed to an RX2 series high-function general-purpose inverter, it provides support for 100-Mbps EtherCAT.

Common Specifications

Item Specifications
Model 3G3AX-RX2-ECT
Power supply Supplied from the inverter
Protective structure Open type (IP20)
Ambient operating temperature -10 to 50°C
Ambient storage temperature -20 to 65°C
Ambient operating humidity 20% to 90% (with no condensation)
Vibration *1 5.9 m/s2 (0.6 G), 10 to 55 Hz
Application environment Indoors (There should be no corrosive gas, oil mist, or metal dust.)
Weight 100 g max. (Shipping weight: approx. 200 g)
Applicable standards Conformance to EU Directives and UK legislation, UL/cUL, CSA, KC, RCM

*1. When using the EtherCAT Communication Unit with the inverters listed below, install the unit where it is not subjected to
      vibration or shock.
      Vibration or shock can cause communication errors or malfunctions.
      Applicable models: 3G3RX2-A2300 to A2550, 3G3RX2-A4300 to B413K

EtherCAT Communications Specifications

Item Specifications
Communications standard IEC 61158 Type12, IEC 61800-7 CiA 402 drive profile
Physical layer 100BASE-TX (IEEE802.3)
Connector RJ45 × 2 (shielded type)
ECAT IN: EtherCAT input
ECAT OUT: EtherCAT output
Communications media Category 5 or higher (cable with double, aluminum tape and braided shielding) is
recommended.
Communications distance Distance between nodes: 100 m max.
Process data Fixed PDO mapping
User PDO mapping
Mailbox (CoE) Emergency messages, SDO requests, and SDO responses
Synchronization mode FreeRun mode *1
LED display L/A IN (Link/Activity IN) × 1
L/A OUT (Link/Activity OUT) × 1
RUN × 1
ERR × 1
CiA402 drive profile Velocity mode

*1. In FreeRun mode, slaves perform I/O processing, i.e., refresh I/O data asynchronously with the communications cycle of
      the master. The communications cycle is determined by the cycle time of the master. For the communications response
      time of the EtherCAT Communication Unit, refer to the EtherCAT Communication Unit User’s Manual (Cat.No. I663) for
      details.
Note that FreeRun mode in the synchronization mode has a different meaning from free-run stop of an Inverter.

Version Information

The following table gives the relationship between unit versions of EtherCAT Communication Unit and the corresponding Sysmac Studio versions.

EtherCAT Communication Unit version Sysmac Studio
Ver. 1.0 or later Ver. 1.47 or higher